pt. USAHA JAYAMAS BHAKTI

Product Detail

TANK SENTINEL ®: Automatic Tank Gauges

The INCON automatic tank gauging systems provide environmental compliance, inventory, and leak detection information for up to eight underground storage tanks.

CAPABILITIES
The INCON Automatic Tank Gauges (ATG) have
programmable settings and are capable of monitoring up to 8 tanks.

· Offers a wide range of advanced communications options.

· Expanded, backlit LCD display with two lines of forty columns.

· Supports multiple languages.

· Supports English and Metric Units.

· Generates numerous system warnings and tank alarms to quickly notify the user of any potential problem.

· Supports important generator and fuel management features.

FEATURES

· a wide range of applications.

· Easily programmed through multi-purposeCan monitor up to eight tanks.

· Designed on an open architecture platform that is easily expandable for additional capabilities.

· Low cost, compact console handles  function keys to meet site-specific criteria.

· Generates inventory, compliance, and fuel management reports.

· Internal high-speed fax/data modem capability allows remote access from System Sentinel™.

· Executes automatic system check and notifies user if the unit is not functioning properly.

· Performs continuous leak testing – no station down time required.

SPECIFICATION

* Total number including additional options

TS-1001/TS-1001/G

To contact us:

PT. USAHA JAYAMAS BHAKTI

Jl. Indokarya II Blok G No. 1-9

Jakarta Utara—INDONESIA

Phone +62 21 658 37136

Fax. +62 21 65837144-45

mail@usahajb.com

www.usahajb.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT MODEL

TS-1001

TS-1001/G

TS-2001

Dimensions

12”H x 11”W x 4”D

12”H x 11”W x 4”D

12”H x 17”W x 6”D

Input Channels

2(10*)

2(10*)

2(26*)

Output Only Channels

2(10*)

2(10*)

2(26*)

Sensor inputs

12(28*)

12(28*)

24(40*)

Generator Back Up

No

Yes

No

Number of tanks monitored

4

2

8

The following specifications apply to all models:

Display type

Alpha-numeric LCD

Applicable liquids

 

Petroleum, chemicals, and hazardous waste

Level units

 

Inches or centimeters

Temperature units

 

Degrees Fahrenheit or Celsius

Volume units

 

Gallons or Liters

Number of LLDs supported

 

8

Display size

 

2 lines of 40 characters

Printer type

 

24 column thermal

Power requirements

 

115 VAC +15%, -10%, 100 Watts Maximum, 1 Amp Maximum
230 VAC +15%, -10% (Special Order), 100 Watts Maximum, 0.5 Amp Maximum

Operating Temperature

 

32° to 122°F (0° to 50°C)

Storage Temperature

 

-4° to 140°F (-20° to 60°C)

Intrinsic Safety Rating

 

Class I, Div. 1, Group D

APPLICATIONS

This ATG has been designed to monitor tank tightness, gather inventory information and assist with multiple environmental compliance issues.

• 

Third-party approved volumetric leak detection
(Pd=99.9% at 0.2 gph).

Provides accurate inventory information, including a “days supply remaining” report which can be used to better-schedule deliveries.

Can provide dispenser information and automate reconciliation when used in conjunction with the INCON TS-DIM.

Multi-purpose relays which can be used for outputs to overfill alarms and external audible and visual indicators.